Procedure 5-55: Clear "inc. (from fiber) DSn RAI" alarms

- Overview

This procedure is used to clear the following alarms:

  • inc. (from fiber) DS1 RAI

  • inc. (from fiber) DS3 RAI

- Before you begin

Prior to performing this task:

  1. Refer to Before you begin and Required equipment in this chapter.

  2. Refer to Electrostatic discharge in Chapter 1, Safety.

Task

Complete the following steps to clear an inc. (from fiber) DSn RAI alarm.

 
1

From the WaveStar® CIT System View, click the Alarm List button and locate the inc. (from fiber) DSn RAI alarm in the resulting alarm list.


2

Refer to the Probable Cause column in the alarm list, determine the affected port, and note the corresponding AID.


3

Using circuit layouts and/or office records, identify the other network element where the alarmed DSn is terminated.


4

Important!

A likely cause of the inc. (from fiber) DSn RAI alarm at the local network element is a problem/failure at the interfacing customer equipment that is connected to the far-end SONET network element.

Follow local procedures for addressing any DSn-related conditions/alarms at the interfacing customer equipment that is connected to the far-end SONET network element.


End of steps