Prior to performing this procedure:
Refer to Before you begin and Required equipment in this chapter.
Refer to Electrostatic discharge in Chapter 1, Safety.
Obtain office records showing the correct port provisioning values for the affected local port.
Complete the following steps to clear an inc. (from fiber) DSn alarm.
1 |
From the WaveStar® CIT System View, click the Alarm List button and locate the inc. (from fiber) DSn alarm in the resulting alarm list. | ||||||
2 |
Refer to the Probable Cause column in the alarm list, determine the affected port, and note the corresponding AID. | ||||||
3 |
Select View → Equipment to access the affected port and click Select. Result: The port parameters appear. | ||||||
4 |
Compare the provisioned port parameter values with office records. If the local port is provisioned incorrectly, select Configuration → Equipment to access the affected port and click Select. Provision the port parameters as required and click Apply. Then click Close. | ||||||
5 |
From the System View, click the Alarm List button and click Refresh. | ||||||
6 |
Is the inc. (from fiber) DSn alarm still present?
| ||||||
7 |
Using circuit layouts and/or office records, identify the other network element where the alarmed DSn is terminated. | ||||||
8 |
Important! A likely cause of an inc. (from fiber) DSn alarm at the local network element is a problem/failure at either the far-end SONET network element or the interfacing customer equipment connected to the far-end SONET network element. Follow local procedures for addressing any DSn-related alarms/conditions at the far-end SONET network element or the interfacing customer equipment connected to the far-end SONET network element. End of steps |