Prior to performing this procedure:
Refer to Before you begin and Required equipment in this chapter.
Refer to Laser safety and Electrostatic discharge in Chapter 1, Safety.
Complete the following steps to identify and clear a Ring Circuit Alarm Suppressed condition.
1 |
From the WaveStar® CIT System View, click the Alarm List button and locate the Ring Circuit Alarm Suppressed condition in the resulting alarm list and note the corresponding AID. |
2 |
From the System View, select Configuration → Equipment, select the Ptn Grp tab, highlight the 2F BLSR and click Select. Result: The Configure Equipment window opens. |
3 |
In Configure Equipment window, change Ring Circuit Alarm Mode to Enabled. Click Apply and Close. |
4 |
From the System View, click the Alarm List button and click Refresh. Result: The Ring Circuit Alarm Suppressed condition is no longer present. End of steps |