inc. DS1 sync. ref. LOF

Description

The system has detected a DS1 loss-of-frame (LOF) condition for the incoming DS1 synchronization reference signal.

Alarm Data

Value/Meaning

Severity Levels

Critical (CR), Major (MJ), Minor (MN), Not Alarmed (NA), Not Reported (NR)

Unprotected default: Major (MJ)

Protected default: Minor (MN)

ASAP Type

System Timing

AID Type

Synch reference (external)

Date

Month/day/year that the condition was detected

Time

Hour:minute:second that the condition was detected

Probable Cause

SYNCOOS (Loss of timing on both primary and secondary synchronization references)

SYNC (Loss of timing on a protected synchronization reference)

Effect on Service

NSA

Alarm Entity Type

T1

Description

inc. DS1 sync. ref. LOF

Likely Cause

Failure of the timing supply that provides the DS1 timing reference.

Visible Indication

Lighted CR, MJ, or MN LED on the SYSCTL faceplate (when the severity level is provisioned to Critical, Major, or Minor, respectively) and a flashing Fault LED on the alarmed circuit pack.

Action

Proceed to Procedure 5-49: Clear "inc. DS1/E1 sync. ref." alarms.

November 2011Copyright © 2011 Alcatel-Lucent. All rights reserved.