At least 128 consecutive zeros are received in the DS3 signal incoming from the DSX-3, or the energy at the DS3 input is below a preset threshold.
Alarm Data |
Value/Meaning |
---|---|
Severity Levels |
Critical (CR), Major (MJ), Minor (MN), Not Alarmed (NA), Not Reported (NR) Default: Critical (CR) |
ASAP Type |
DS3 Port |
AID Type |
DS3 Port |
Date |
Month/day/year that the condition was detected |
Time |
Hour:minute:second that the condition was detected |
Probable Cause |
LOS (Loss of signal) |
Effect on Service |
SA or NSA |
Alarm Entity Type |
T3 |
Description |
inc. (from DSX) DS3 LOS |
Likely Cause |
Hard failure of upstream terminal equipment or facility (towards the DSX-3), The DS3 input was disconnected at either the backplane or DSX-3, or The DSX-3 equipment is failed. |
Visible Indication |
Lighted CR, MJ, or MN LED on the SYSCTL faceplate (when the severity level is provisioned to Critical, Major, or Minor, respectively) and a flashing Fault LED on the alarmed circuit pack. |
Action |
Proceed to Procedure 5-51: Clear "inc. (from DSX) DS3" alarms. |