inc. (from DSX) DS3 RAI

Description

The system has detected an incoming Remote Alarm Indication (RAI) at the specified local DS3 port.

Alarm Data

Value/Meaning

Severity Levels

Critical (CR), Major (MJ), Minor (MN), Not Alarmed (NA), Not Reported (NR)

Default: Not Alarmed (NA)

ASAP Type

DS3 Port

AID Type

DS3 Port

Date

Month/day/year that the condition was detected

Time

Hour:minute:second that the condition was detected

Probable Cause

RAI (Remote alarm indication)

Effect on Service

NSA

Alarm Entity Type

T3

Description

inc. (from DSX) DS3 RAI

Likely Cause

A remote incoming signal failure was detected at the interfacing customer equipment that terminates the DS3 path.

Visible Indication

Lighted CR, MJ, or MN LED on the SYSCTL faceplate (when the severity level is provisioned to Critical, Major, or Minor, respectively) and a flashing Fault LED on the alarmed circuit pack.

Action

Proceed to Procedure 5-53: Clear "inc. (from DSX) DSn RAI" alarm.

November 2011Copyright © 2011 Alcatel-Lucent. All rights reserved.