1 |
From the WaveStar® CIT System View, click the Alarm List button and locate the Pluggable Transmission Module removed alarm in the resulting alarm list.
|
2 |
Determine the alarm level for the Pluggable Transmission Module removed alarm. Clear the alarms in order of severity.
|
3 |
Refer to the Probable Cause column in the alarm list, and note the corresponding socket AID.
|
4 |
Using office records, determine if the required socket should contain a pluggable transmission module.
|
5 |
Do office records show that the required socket should contain a pluggable transmission module?
If... |
Then... |
Yes, |
Obtain the missing pluggable transmission module and install it into the required slot.
Refer to the pluggable transmission module installation procedure in the Alcatel-Lucent 1665 Data Multiplexer Extend (DMXtend) User Operations Guide, 365-372-325. |
No, |
Perform the following:
-
Use View → Cross-Connections to obtain a current list of cross-connections. If required, use Configuration → Cross-Connections to access the Cross-Connection Wizard and delete any cross-connections to the affected pluggable transmission module.
-
Select Configuration → Update System → Update All.
A dialog box appears asking you to confirm executing this command. Click Yes.
This system update clears the Pluggable Transmission Module removed alarm. |
End of steps |