1 |
On the equipment tree, expand Network→NE→ Shelf→Synchronization→Clock 32.
|
2 |
On the General tab, configure the PTP Profile parameter as IEC-61850.9.3.
|
3 |
Configure the Clock Type parameter, as required.
Note: Master clock is only supported for 7705 SAR devices with integrated GNSS.
|
4 |
Verify that the default values are correct for the following parameters: Domain, Network Type, Clock ID, Clock Announce Rx Timeout, and Clock Announce Interval.
|
5 |
To turn up PTP ports on the IEC-61850.9.3 PTP clock:
-
Click on the IEEE PTP Port tab. The IEEE 1588 PTP clock form opens.
-
Select a port and configure the required parameters.
-
Verify that the default values for the Cfg Sync Rate and Cfg Delay Req Rate parameters are configured as 1 pkt/sec.
-
Save your changes.
|
6 |
Save your changes and close the forms.
You can view the statistics for the PTP clock on the Statistics tab of the PTP clock form.
End of steps |