Prior to performing this procedure, refer to Required equipment and Before you begin in this chapter.
Complete the following steps to identify and clear an AGNE communication failure alarm.
1 |
From the WaveStar® CIT System View, select Administration → View NE Administration, to check the provisioning of the AGNE for that NE's alarm group. Result: The View NE Administration window opens. | ||||||
2 |
Is the local NE the alarm gateway network element (AGNE)? Alarm Gateway: ENABLED.
| ||||||
3 |
Can you determine the AGNE for the alarm group?
| ||||||
4 |
Is Remote NE status enabled for the AGNE?
| ||||||
5 |
Log into each NE in the alarm group and select Administration → View NE Administration from the System View. | ||||||
6 |
Is Remote NE status enabled?
| ||||||
7 |
From the System View, select Administration → Set NE. Result: The Set NE window opens. | ||||||
8 |
For Remote NE Status, select Enabled to enable Remote NE Status. Important! Note that Remote NE Status must be Enabled in order to provision the alarm group functions. | ||||||
9 |
For Alarm Gateway, select Enabled to provision one NE in the alarm group as the alarm gateway network element (AGNE). Otherwise, select No. | ||||||
10 |
Enter or select the Alarm Group number (1–255) being assigned to the alarm group for this NE. Important! The Alarm Group number must be the same for all NEs in that alarm group. | ||||||
11 |
Ensure the other parameters in the window have not been changed, unless you are provisioning them also. Click OK at the bottom of the window. | ||||||
12 |
Read the warning message, then click Yes to execute the command. Important! An AGNE communication failure alarm may occur if an AGNE has not yet been provisioned for the alarm group. If you need to clear the alarm, select Administration → Set NE, then select Disabled to disable the Remote NE Status. You will have to enable the remote NE status again once the AGNE has been established in order for this NE to be part of the alarm group. | ||||||
13 |
From the WaveStar® CIT System View, click the Alarm List button and click Refresh. Result: The AGNE communication failure alarm is no longer present. End of steps |
November 2011 | Copyright © 2011 Alcatel-Lucent. All rights reserved. |