Prior to performing this procedure:
Refer to Before you begin and Required equipment in this chapter.
Refer to Laser safety and Electrostatic discharge in Chapter 1, Safety.
Complete the following steps to clear a incompatible CP versionalarm.
1 |
From the WaveStar® CIT System View, click the Alarm List button and locate the incompatible CP version alarm in the resulting alarm list. |
2 |
Refer to the Probable Cause column in the alarm list, determine the affected circuit pack, and note the corresponding slot AID. |
3 |
Important! An older version of the LNW27 OC-48 OLIU circuit pack was inserted into a slot that contained a newer version of the LNW27 OC-48 OLIU circuit pack. Select Reports → Equipment Lists → Pack. Select Shelf and click Select to obtain the Circuit Pack List. Observe the correct circuit pack version for the required slot. |
4 |
Replace the old version of circuit pack currently in the required slot with the correct version of the circuit pack. Reference: Procedure 6-5: Replace high-speed main OLIU circuit pack End of steps |