Use this procedure to replace the following circuit packs:
Important!
The high density LNW19/LNW19B 48DS3/EC1 and LNW20 TMUX circuit packs are only compatible with the Alcatel-Lucent 1665 DMX High Capacity Shelf (DMX-HC-20A, DMX-HC-30A, or DMX-HC-30A-CE Shelf Type). The standard Alcatel-Lucent 1665 DMX Shelf does not support the high density LNW19/LNW19B 48DS3/EC1 and LNW20 TMUX circuit packs. If a high density LNW19/LNW19B 48DS3/EC1 or LNW20 TMUX circuit pack is installed in the standard Alcatel-Lucent 1665 DMX Shelf, the system will not recognize the circuit pack as an allowable type.
The system does not support mixing LNW16/19/19B and LNW18/LNW20 circuit packs in the same function group.
The system does not support mixing standard density LNW16/LNW18 and high density LNW19/LNW19B/LNW20 circuit packs in the same function group.
Important!
If both the original circuit pack and the replacement circuit pack fail when no other transmission circuit packs are installed in the shelf, replace the SYSCTL circuit pack. Refer to Procedure 6-10: Upgrade or replace SYSCTL (LNW2) circuit pack.
Prior to performing this procedure:
Refer to Required equipment in this chapter.
Refer to Electrostatic discharge information in Chapter 1, Safety.
Ensure that the appropriate DS3/EC-1/TMUX circuit pack is available for replacement.
Complete the following steps to replace DS3/EC-1/TMUX circuit pack.
1 |
From the System View menu, select View → Protection to view the current protection on the circuit pack you are replacing. | ||||||
2 |
Does 1+1 Equip appear next to the circuit pack that you wish to replace?
| ||||||
3 |
Highlight the Function Unit (for example: 1+1 Equip Fn-d represents Function Unit D) that contains the circuit pack that you are replacing and click Select. | ||||||
4 |
Does the Circuit Pack State for the circuit pack that you wish to replace read In Service?
| ||||||
5 |
From the System View menu, select Fault → Protection Switch. | ||||||
6 |
Highlight the Function Group that contains the circuit pack that you are replacing and click Select. Result: On the right side of the Switch Protection window, the Switch Type: pull-down menu appears. | ||||||
7 |
From the Switch Type: pull-down menu, select Forced and click Apply. Result: A confirmation window appears: "Execution of provision may affect the NE service. Do you want to execute this command?" | ||||||
8 |
On the confirmation window, click Yes to ensure that service switches to the other circuit pack in the Function Group. Click Close on the Switch Protection window. | ||||||
9 |
To verify that the switch has occurred:
| ||||||
10 |
Remove the circuit pack by grasping the inner edge of the locking-levers, and applying a constant pressure, pull the levers forward and remove the circuit pack. | ||||||
11 |
Seat the replacement circuit pack in the vacated Function Unit slot by applying steady pressure to both faceplate latches. Result: FAULT LED on the circuit pack lights for approximately 20 seconds, then goes off. ACTIVE LED remains off. However, if your circuit pack was in-service and unprotected (refer to Step 2), then the FAULT LED on your replacement pack flashes until the signal is verified to be free of errors. (Firmware updates may take place that add additional wait time.) Select View → Refresh System View and the circuit pack appears in the WaveStar® CIT System View indicating successful installation. | ||||||
12 |
From the System View menu, click the Alarm List button to obtain an NE Alarm List. Verify that no alarms are present for the installed circuit pack. If required, refer to the appropriate procedure to clear any alarms. | ||||||
13 |
Do you wish to restore the original Active/Standby states?
| ||||||
14 |
From the System View menu, select Fault → Protection Switch. | ||||||
15 |
Highlight the Function Group that you force-switched and click Select. Result: On the right side of the Switch Protection window, the Switch Type: pull-down menu appears. | ||||||
16 |
From the Switch Type: pull-down menu, select Reset and click Apply. Result: A confirmation window appears: "Execution of provision may affect the NE service. Do you want to execute this command?" | ||||||
17 |
On the confirmation window, click Yes to ensure that forced switch is released. Click Close on the Switch Protection window. | ||||||
18 |
To verify that the forced switch is removed:
| ||||||
19 |
Do you wish to restore the original Active/Standby states?
| ||||||
20 |
From the System View menu, select Fault → Protection Switch. | ||||||
21 |
Highlight the Function Group and click Select. Result: On the right side of the Switch Protection window, the Switch Type: pull-down menu appears. | ||||||
22 |
From the Switch Type: pull-down menu, select Manual and click Apply. Result: A confirmation window appears: "Execution of provision may affect the NE service. Do you want to execute this command?" | ||||||
23 |
On the confirmation window, click Yes to ensure that service switches to the other circuit pack in the Function Group. Click Close on the Switch Protection window. | ||||||
24 |
To verify that the switch has occurred:
| ||||||
25 |
From the System View menu, click the Alarm List button to obtain an NE Alarm List. Verify that no alarms are present for the installed circuit pack. If required, refer to the appropriate procedure to clear any alarms. | ||||||
26 |
From the System View menu, use View → Equipment to access the circuit pack/port parameters for the circuit pack just installed and verify that the parameters are intact. If required, refer to the appropriate procedure in the Alcatel-Lucent 1665 Data Multiplexer (DMX) User Operations Guide, 365-372-301 to change any circuit pack/port parameters. End of steps |
November 2011 | Copyright © 2011 Alcatel-Lucent. All rights reserved. |