Prior to performing this procedure:
Refer to Before you begin and Required equipment in this chapter.
Refer to Laser safety and Electrostatic discharge in Chapter 1, Safety.
Complete the following steps to clear a CP not allowed - eqpt alarm.
1 |
From the WaveStar® CIT System View, click the Alarm List button and locate the CP not allowed - eqpt alarm in the resulting alarm list. | ||||||
2 |
Determine the alarm level(s) for the active CP not allowed - eqpt alarm(s). Clear the alarms in order of severity. | ||||||
3 |
Refer to the Probable Cause column in the alarm list, determine the affected circuit pack, and note the corresponding slot AID. | ||||||
4 |
Using office records, determine the correct circuit pack type for the required slot. | ||||||
5 |
From the System View, select Reports → Equipment Lists → Pack. Select Shelf and click Select to obtain the Circuit Pack List. Observe the circuit pack information for the required slot. | ||||||
6 |
Compare the correct circuit pack information from office records with the circuit pack information from the Circuit Pack List and the circuit pack that is physically in the required slot. | ||||||
7 |
Is the correct circuit pack physically installed in the required slot?
End of steps |