Procedure 5-29: Clear "ERP - PDU Watchdog Timeout" alarm

- Overview

This procedure is used to clear an ERP - PDU Watchdog Timeout alarm.

- Before you begin

Prior to performing this procedure:

  1. Refer to Before you begin and Required equipment in this chapter.

  2. Refer to Laser safety and Electrostatic discharge in Chapter 1, Safety.

  3. Obtain office records identifying the nodes in the ring and the correct Ethernet ring protection provisioning.

Steps

Complete the following steps to clear an ERP - PDU Watchdog Timeout alarm.

 
1

From the WaveStar® CIT System View, click the Alarm List button and locate the ERP - PDU Watchdog Timeout alarm in the resulting alarm list and note the corresponding AID.


2

Using office record determine if this node is the RPL owner node.

If this node is ...

Then...

the RPL owner node,

From the System View, select Configuration → Data → Create/Modify/Delete ERP to access the required Ethernet circuit pack/ring. Disable the ERP State parameter, and then Enable the ERP State parameter.

Proceed to Step 10

a non-RPL owner node,

Continue with the next step.


3

From the System View, select View → Data → ERP. Select the required Ethernet circuit pack and click Select.

Result:

The ERP information appears.


4

Important!

The local node may be using the wrong VLAN or MD level.

Compare the provisioned values of the provisionable ERP parameters with office records to verify that the provisioned values are correct.

If the provisionable ERP parameters...

Then...

correct,

Proceed to Step 7.

not correct,

From the System View, select Configuration → Data → Create/Modify/Delete ERP to access the required Ethernet circuit pack/ring and provision the ERP parameters according to office records. Then continue with the next step.


5

From the System View, click the Alarm List button and click Refresh.


6

Is the ERP - PDU Watchdog Timeout condition still present?

If...

Then...

Yes

Continue with the next step.

No

STOP! End of Procedure.


7

Important!

Only one RPL owner node is required in the ring. There may be no RPL Owner node provisioned (or it is disabled).

Using office records determine which node in the ring is the designated RPL owner node.


8

Log in to the designated RPL owner node (according to office records) and verify that the provisionable ERP parameters are provisioned correctly.

If the node is a...

Then...

Alcatel-Lucent 1665 DMXtend

From the System View, select View → Data → ERP and the required Ethernet circuit pack to obtain Ethernet ring protection provisioning.

If required, select Configuration → Data → Create/Modify/Delete ERP and the required Ethernet circuit pack to reprovision the ERP parameters.

another product,

Use product's documentation to log in and obtain the required port/VCG Ethernet ring protection provisioning information.

If required reprovision the ERP parameters.

Reference:

Procedure 6-2: Connect Personal Computer (PC) and establish WaveStar® CIT session


9

From the System View, click the Alarm List button and click Refresh.


10

Is the ERP - PDU Watchdog Timeout condition still present?

If...

Then...

Yes

Contact your next level of support.

No

STOP! End of Procedure.


End of steps