Procedure 5-33: Clear "far end not LCAS" condition

- Overview

This procedure is used to clear the far end not LCAS condition.

- Before you begin

Prior to performing this procedure:

  1. Refer to Before you begin and Required equipment in this chapter.

  2. Refer to Laser safety and Electrostatic discharge in Chapter 1, Safety.

Steps

Complete the following steps to clear a far end not LCAS condition.

 
1

From the WaveStar® CIT System View, click the Alarm List button and locate the far end not LCAS condition in the resulting alarm list and note the corresponding VCG AID.


2

Using circuit layouts and/or office records, identify the far-end network element for the specified VCG.


3

Use the WaveStar® CIT to log in to the required far-end Alcatel-Lucent 1665 DMXtend for the specified VCG.

Reference:

Procedure 6-2: Connect Personal Computer (PC) and establish WaveStar® CIT session


4

From the System View, select Reports → Equipment Lists → Pack. Select Shelf and click Select.

Result:

The Circuit Pack List appears.


5

Important!

The LNW63 GBE PL Gigabit Ethernet, LNW70 100/1G-FXS Gigabit Ethernet and LNW74 10/100 Base FX/TX Enhanced Private Line Ethernet circuit packs support LCAS operation.

Using the Circuit Pack List and office records, determine if the far-end Alcatel-Lucent 1665 DMXtend supports LCAS.


6

If the far-end Alcatel-Lucent 1665 DMXtend...

Then...

supports LCAS and LCAS operation is desired,

go to Step 7 and enable LCAS for the required VCG at the far end.

supports LCAS and LCAS operation is not desired,

Disconnect the WaveStar® CIT from the far-end Alcatel-Lucent 1665 DMXtend and go to Step 10 to disable LCAS on the required VCG at the near end (local).

does not support LCAS,

Disconnect the WaveStar® CIT from the far-end Alcatel-Lucent 1665 DMXtend and go to Step 10 to disable LCAS on the required VCG at the near end (local).


7

From the System View at the far end, select Configuration → Equipment. Expand the required Ethernet circuit pack details and select the required VCG port being provisioned. Click Select.


8

Select the LCAS tab. Provision the LCAS parameters, as required. Click Apply.

Result:

A dialog box appears asking you to confirm executing this command. Click Yes. Click Close to exit window.


9

Disconnect the WaveStar® CIT from the far-end Alcatel-Lucent 1665 DMXtend.

STOP! End of Procedure.


10

From the System View at the near end, select Configuration → Equipment. Expand the required Ethernet circuit pack details and select the required VCG port being provisioned. Click Select.


11

Select the LCAS tab and disable the LCAS mode. Click Apply.

Result:

A dialog box appears asking you to confirm executing this command. Click Yes. Click Close to exit window.


End of steps