Prior to performing this procedure:
Refer to Before you begin and Required equipment in this chapter.
Refer to Electrostatic discharge in Chapter 1, Safety.
Obtain office records that show the correct ring connections and required cross-connections.
Complete the following steps to clear the RPR Miscabling condition.
1 |
From the WaveStar® CIT System View, click the Alarm List button and locate the RPR Miscabling condition in the resulting alarm list and note the corresponding VCG AID. | ||||||
2 |
Select View → Cross-Connections. Expand the required circuit pack details and select the affected VCG port. Click Select to obtain a list of cross-connections. Observe the provisioned cross-connections and compare with office records. | ||||||
3 |
| ||||||
4 |
Select Configuration → Cross-Connections to access the Cross-Connection Wizard. Use the Cross-Connection Wizard to delete the existing wrong cross-connections and then create the correct new cross-connections according to office records. STOP! End of Procedure. | ||||||
5 |
Using office records, identify and log in to the adjacent node. Reference: Procedure 6-2: Connect Personal Computer (PC) and establish WaveStar® CIT session | ||||||
6 |
Select View → Cross-Connections. Expand the required circuit pack details and select the affected VCG port. Click Select to obtain a list of cross-connections. Observe the provisioned cross-connections and compare with office records. | ||||||
7 |
Select Configuration → Cross-Connections to access the Cross-Connection Wizard. Use the Cross-Connection Wizard to delete the existing wrong cross-connections and then create the correct new cross-connections according to office records. End of steps |