The following equipment is required:
Important!
In central office applications, the fan unit must equipped with a fan filter. To keep the fan unit operating properly, it is recommended that users routinely change the fan filter every 6 to 9 months.
In outside plant (OSP) applications, remove the fan filter. Operating Alcatel-Lucent 1665 DMXtend in an OSP without the fan filter improves air flow and therefore enhances cooling performance and extends the life of the equipment.
Prior to performing this procedure, refer to Electrostatic discharge in Chapter 1, Safety.
Complete the following steps to replace the fan filter.
1 |
Remove the fan filter by pulling it towards you. The fan unit is installed on the right side of the Alcatel-Lucent 1665 DMXtend shelf. The fan filter is located to the right of the Alcatel-Lucent 1665 DMXtend fan unit (see Figure 6-18, Alcatel-Lucent 1665 DMXtend fan filter). Figure 6-18: Alcatel-Lucent 1665 DMXtend fan filter![]() |
2 |
Install a new filter into the fan filter slot. End of steps |