In addition to the equipment listed in Required equipment, the following equipment is also required:
Prior to performing this procedure:
Refer to Before you begin in this chapter.
Refer to Electrostatic discharge in Chapter 1, Safety.
Complete the following steps to clear a fan shelf failed or hardware failure alarm.
1 |
Are the power indicator (PWR ON) LEDs lighted on the Alcatel-Lucent 1850 TSS-5 fan unit?
| ||||||
2 |
The fan unit has no power. Check power and alarm cables. If cables are not connected, install power and alarm cables to the shelf and tighten screw locks. | ||||||
3 |
Is the fan unit running and working properly (PWR ON LEDs lighted, FAN FAULT LED off)? The Alcatel-Lucent 1850 TSS-5 fan unit needs three fans operating to provide the minimum required airflow.
| ||||||
4 |
Unscrew the captive screw that secures the fan unit to the shelf chassis. | ||||||
5 |
Slide the old fan unit out from shelf chassis. | ||||||
6 |
Slide the new fan unit back into the shelf chassis. Tighten the captive screw. End of steps |