Procedure 5-116: Clear "PROTN Port Failure/Protection CP Input fault" alarms

- Overview

This procedure is used to clear the following alarms:

  • Protection CP Input fault

  • PROTN DS3 Port Failure

  • PROTN EC1 Port Failure

- Before you begin

Prior to performing this procedure:

  1. Refer to Before you begin and Required equipment in this chapter.

  2. Refer to Electrostatic discharge in Chapter 1, Safety.

Steps

Complete the following steps to clear a PROTN Port Failure/Protection CP Input fault alarm.

 
1

From the WaveStar® CIT System View, click the Alarm List button and locate the PROTN Port Failure/Protection CP Input fault alarm in the resulting alarm list.


2

Refer to the Probable Cause column in the alarm list, determine the affected port and circuit pack, and note the corresponding AIDs.


3
DANGER 

NOTICE

Service-disruption hazard

Replacing circuit packs may disrupt service.

Before taking action, determine the extent of service disruption caused by replacing a circuit pack. Then, perform the action(s) deemed appropriate in light of the traffic being carried and the nature of the failure.

Replace the affected circuit pack.

Reference:


4

From the System View, click the Alarm List button and click Refresh.


5

Is the PROTN Port Failure/Protection CP Input fault alarm still present?

If...

Then...

Yes

Remove the replacement circuit pack and return the original circuit pack to the slot, then continue with Step 6.

No

STOP! End of Procedure.


6
DANGER 

NOTICE

Service-disruption hazard

Disconnecting cables may disrupt service.

Before taking action, determine the extent of service disruption caused by disconnecting cables. Then, perform the action(s) deemed appropriate in light of the traffic being carried and the nature of the failure.

Check cable connections between the shelf backplane and the local cross-connect panel or equivalent connection point for faulty connections or damage and repair/replace as necessary.

If a visual inspection does not reveal any problems, you may consider making an electrical measurement per local operating instructions.


7

From the System View, click the Alarm List button and click Refresh.


8

Is the PROTN Port Failure/Protection CP Input fault alarm still present?

If...

Then...

Yes

Continue with Step 9.

No

STOP! End of Procedure.


9

If...

Then...

PROTN DS3 Port Failure

Determine and record the signal format of the interfacing customer port connected to the alarmed port on the local network element and then continue with Step 10.

PROTN EC1 Port Failure

Proceed to Step 14.


10

From the Alcatel-Lucent 1665 DMX System View, select View → Equipment, expand the pack, highlight the alarmed port, and click Select.


11

Compare the signal format of the local port against the information determined about the interfacing customer port. If there are inconsistencies, determine the correct provisioning and correct according to local procedures.

If the local port is provisioned incorrectly, from the System View, select Configuration → Equipment, expand the pack, highlight the alarmed port, and click Select. Provision the Signal Format appropriately, click Apply, and then click Close.


12

From the System View, click the Alarm List button and click Refresh.


13

Is the PROTN Port Failure/Protection CP Input fault alarm still present?

If...

Then...

Yes

Continue with Step 14.

No

STOP! End of Procedure.


14

Important!

A likely cause of the PROTN Port Failure/Protection CP Input fault alarm at the local network element is a failure at the interfacing customer port or a problem with the cabling/wiring between systems.

Follow local procedures to isolate and clear the trouble.


End of steps

November 2011Copyright © 2011 Alcatel-Lucent. All rights reserved.