Procedure 5-135: Clear "Subshelf-related" alarms/conditions

- Overview

This procedure is used to clear the following subshelf-related alarms/conditions:

  • Invalid Subshelf Configuration

  • Multiple Main Shelf TIDs

  • Subshelf Boot Failed

  • Subshelf Configuration Mismatch

- Before you begin

Prior to performing this procedure:

  1. Refer to Before you begin and Required equipment in this chapter.

  2. Refer to Electrostatic discharge in Chapter 1, Safety.

  3. Obtain office records specifying the required main shelf/subshelf provisioning.

  4. Obtain office records specifying the required valid generic.

  5. Locate the most recent backup copy of the network element database in case it is necessary to restore the network element database.

Steps

Complete the following steps to clear subshelf-related alarms/conditions.

 
1

Important!

When the shelf is in the Maintenance Mode state, the IND display on the SYSCTL circuit pack faceplate shows MPx.x (where x.x is the generic number).

If the shelf is in the Maintenance Mode state, the default User IDs/passwords must be used to log in to the network element. LUC01, LUC02, and LUC03 are the default privileged User IDs, and DMX2.5G10G is the default privileged password.

Perform the following to log in to the shelf using the WaveStar® CIT TL1 Cut-Tthrough Mode.

  1. From the Network View, log into the shelf but this time click TL1, not Graphical.

  2. Select the Cut Through Execution Mode and click OK.

  3. Enter a default privileged User ID and password. Defaults are LUC01 and DMX2.5G10G, respectively.

Reference:

Alcatel-Lucent 1665 Data Multiplexer (DMX) TL1 Message Details, 365-372-306


2

Execute the rtrv-alm-all TL1 command to obtain a list of active alarms.

Reference:

Alcatel-Lucent 1665 Data Multiplexer (DMX) TL1 Message Details, 365-372-306


3

Observe the list of active alarms.

If...

Then...

Invalid Subshelf Configuration

Execute the canc-user TL1 command to exit the WaveStar® CIT TL1 Cut-Tthrough Mode, then proceed to Procedure 5-135.1: Clear "Invalid Subshelf Configuration" alarm.

Multiple Main Shelf TIDs

Execute the canc-user TL1 command to exit the WaveStar® CIT TL1 Cut-Tthrough Mode, then proceed to Procedure 5-135.2: Clear "Multiple Main Shelf TIDs" alarm.

Subshelf Boot Failed

Execute the canc-user TL1 command to exit the WaveStar® CIT TL1 Cut-Tthrough Mode, then proceed to Procedure 5-135.3: Clear "Subshelf Boot Failed" alarm.

Subshelf Configuration Mismatch

Proceed to Procedure 5-135.4: Clear "Subshelf Configuration Mismatch" alarm.


End of steps